Parameter Konduktor Bare Al Stranded Overhead
Code Name | Area | Stranding | Approx. Overall Diameter | Weight | Nominal Breaking Load | D.C. Resistance at 20ºC | |
mm² | No. mm² | Dia. mm | mm | kg/km | kN | ohm/km | |
10 | 10 | 7 | 1.35 | 4.05 | 27.4 | 1.95 | 2.8633 |
16 | 16 | 7 | 1.71 | 5.12 | 43.8 | 3.04 | 1.7896 |
25 | 25 | 7 | 2.13 | 6.40 | 68.4 | 4.50 | 1.1453 |
40 | 40 | 7 | 2.70 | 8.09 | 109.4 | 6.80 | 0.7158 |
63 | 63 | 7 | 3.39 | 10.2 | 172.3 | 10.39 | 0.4545 |
100 | 100 | 19 | 2.89 | 12.9 | 274.8 | 17.00 | 0.2877 |
125 | 125 | 19 | 3.27 | 14.5 | 343.6 | 21.25 | 0.2302 |
160 | 160 | 19 | 3.66 | 16.4 | 439.8 | 26.40 | 0.1798 |
200 | 200 | 19 | 4.09 | 18.3 | 549.7 | 32.00 | 0.1439 |
250 | 250 | 19 | 3.29 | 20.5 | 687.1 | 40.00 | 0.1151 |
315 | 315 | 37 | 3.71 | 23.0 | 867.9 | 51.97 | 0.0916 |
400 | 400 | 37 | 3.94 | 26.0 | 1102.0 | 64.00 | 0.0721 |
450 | 450 | 37 | 4.15 | 27.5 | 1239.8 | 72.00 | 0.0641 |
500 | 500 | 37 | 4.39 | 29.0 | 1377.9 | 80.00 | 0.0577 |
560 | 560 | 37 | 3.63 | 30.7 | 1542.9 | 89.60 | 0.0515 |
630 | 630 | 61 | 3.85 | 32.6 | 1738.3 | 100.80 | 0.0458 |
Deskripsi Overhead Bare Al Stranded Conductor
Konduktor: kawat bundar AL
Standar: BS215, IEC61089
Isolasi: tidak berinsulasi
Rentang aplikasi: transmisi dan distribusi daya overhead
Tidak ada atau untai: 7 untai, 19 untai, 37 untai dan 62 untai
Penerapan Overhead Bare Al Stranded Conductor
Kabel ini banyak digunakan untuk jalur distribusi daya dengan jarak pendek dan kemampuan pembawa beban kecil dari tiang. AAC adalah pilihan yang baik untuk sistem transmisi dan distribusi daya overhead. Standar ini mencakup konduktor tembaga yang ditarik keras yang digunakan untuk keperluan listrik dan baja konduktor aluminium yang diperkuat.