Parameter Tahan Api Single Core 300-500V
Nominal Cross Section Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Without Earth Conductor | |
mm² | No./mm | mm | mm | Nominal Overall Diameter mm | Approx. Weight kg/km |
1.5 | 7/0.53 | 0.5 | 0.5 | 4.4 | 29 |
2.5 | 7/0.67 | 0.5 | 0.5 | 4.9 | 40 |
4 | 7/0.85 | 0.5 | 0.5 | 5.5 | 55 |
Deskripsi Fire Resistant Single Core 300-500V
Nilai tegangan: 300 / 500V
Standar dasar: BS 7211
Konduktor: kawat tembaga anil telanjang, kawat pilin ke IEC (EN) 60228 kelas 2
Fire lyer: Pita kaca mika
Isolasi: PVC (XLPE)
Selubung: senyawa LSZH sampai BS 7655-6.1
Kisaran suhu pengoperasian (keadaan tetap): -30 ° C - + 90 ° C
Kisaran suhu pengoperasian (status seluler): -20 ° C - + 50 ° C
Jari-jari lentur min: 6 kali Diameter Keseluruhan
Resistansi isolasi: 20 MΩ x km (pada 20 ° C)
Suhu sirkuit pendek: 250 ° C
Circuit Integrity | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); |
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); | |
NF C32-070-2.3(CR1) | |
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; |
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); | |
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | |
Reduced Fire Propagation (Vertically-mounted bundled wires | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30- |
004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 | |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; |
CEI 20-37/2-1 ; BS 6425-1* | |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; |
CEI 20-37/2-2 ; BS 6425-2* | |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; |
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* | |
No Toxic gases | NES 02-713; NF C 20-454 |
Penerapan Tahan Api Single Core 300-500V
Kabel dirancang untuk fasilitas yang menjaga integritas sirkuit listrik dalam sistem catu daya sangat penting.
Kabel banyak digunakan di terowongan bawah tanah, penerangan darurat, sistem alarm kebakaran, sirkuit kontrol dan daya, pembangkit listrik, lift, eskalator, dan gedung bertingkat tinggi.