Parameter Kabel Daya Tahan Api (1-4cores)
Cross-sectional Area (mm2) | No.&diameter of wire (N/mm) | Average overall diameter (mm) | Reference weight (kg/km) | Conductor Resistance (Ω/km) 20ºC Max |
1.5 | 7/0.52 | 6.6 | 58 | 12.1 |
2.5 | 7/0.67 | 7.1 | 72 | 7.41 |
4.0 | 7/0.85 | 7.6 | 91 | 4.61 |
6.0 | 7/1.04 | 8.3 | 117 | 3.08 |
10 | 7/1.35 | 9.3 | 165 | 1.83 |
16 | 7/1.70 | 10.3 | 229 | 1.15 |
25 | 7/2.24 | 11.6 | 333 | 0.727 |
35 | 19/1.56 | 12.6 | 420 | 0.524 |
50 | 19/1.86 | 14.1 | 564 | 0.387 |
70 | 14/2.55 | 16.2 | 762 | 0.268 |
95 | 19/2.55 | 17.8 | 1010 | 0.193 |
120 | 24/2.55 | 19.6 | 1263 | 0.153 |
150 | 30/2.55 | 21.6 | 1539 | 0.124 |
185 | 37/2.55 | 23.8 | 1910 | 0.0991 |
240 | 48/2.55 | 26.4 | 2463 | 0.0754 |
300 | 60/2.55 | 29 | 3060 | 0.0601 |
400 | 60/2.95 | 32.7 | 3991 | 0.0470 |
Deskripsi Kabel Daya Tahan Api (1-4cores)
• Suhu Terukur: 90 o C
• Nilai Tegangan: 600 / 1000V
• Standar Referensi: IEC60502-1, BS6387, BS7846, IEC60331, IEC60332-1, IEC60332-3, IEC60754, IEC61034
• Model: FR / XLPE / LSZH
• Konduktor tembaga pilin (FR10)
• Pita tahan api Mika / Kaca
• Diisolasi dengan senyawa polietilen ikatan silang
• Tempat tidur LSZH
• LSZH berselubung keseluruhan
Penerapan Kabel Daya Tahan Api (1-4cores)
Untuk pembangkit listrik tenaga nuklir, kereta bawah tanah, terowongan, bandara, dermaga, menara radio dan situasi persyaratan tahan api tinggi lainnya.